Modbus

The modbus node-type uses libmodbus to communicate to devices via Modbus over the RTU or TCP transports.

Prerequisites

This node-type requires libmodbus (>= 3.1.0).

Implementation

The source code of the node-type is available here: https://github.com/VILLASframework/node/blob/master/lib/nodes/modbus.cpp

Configuration

remote
required
string

The hostname or IP of the Modbus TCP device.

port
integer
Default: 1883

The port number of the Modbus TCP device.

unit
integer [ 0 .. 65535 ]

The addressed unit used for serial communication. This is optional for TCP.

Example
{
  • "remote": "example.com",
  • "port": 1883,
  • "unit": 1,
  • "transport": "tcp"
}

Example

node/etc/examples/nodes/modbus.conf
nodes = {
modbus_node = {
type = "modbus"

# Required transport type. Can be either "rtu" or "tcp"
transport = "tcp"

# Optional timeout in seconds when waiting for responses from a modbus server
# Default is 1.0
response_timeout = 1.0


#
# Settings for transport = "tcp"
#

# Required remote IP address
remote = "127.0.0.1"

# Optional remote port
# Default is 502
port = 502


#
# Settings for transport = "rtu"
#

# Required device file
device = "/dev/ttyS0"

# Required baudrate
baudrate = 9600

# Required parity. One of "none", "even" and "odd"
parity = "none"

# Required data bits. One of 5, 6, 7, 8
data_bits = 5

# Required stop bits. One of 1, 2
stop_bits = 1

# The modbus unit ID
# Required for transport = "rtu"
# Optional for transport = "tcp"
unit = 1

# Optional polling rate for the modbus remote reads
# Defaults to 10
rate = 10

in = {
signals = (
# A 32-bit IEEE 754 floating point value
# This spans 2 registers
{
# Required type = "float"
type = "float"

# Required address of the lowest register
address = 0x50

# Optional endianess for joining the 2 16-bit registers into a 32-bit value
# Defaults to "big"
word_endianess = "big"

# Optional endianess for the 2 bytes within a register
# Defaults to "big"
byte_endianess = "big"

# Optional scale that should be applied to the integer value
# Defaults to 1
scale = 10

# Optional offset that should be applied to the integer value after scaling
# Defaults to 0
offset = 2
},
# A single bit within a register as a boolean value
{
# Required type = "boolean"
type = "boolean"

# Required address of the register
address = 0x54

# Required bit within the register
# Starting at 0
bit = 0
},
# An integer value
# This may span multiple registers
{
# Required type = "integer"
type = "integer"

# Required address of the lowest register
address = 0x52

# Optional number of registers that should be joined to form the value
# Defaults to 1
integer_registers = 1

# Optional endianess for joining the 16-bit registers into a 32-bit value
# Defaults to "big"
word_endianess = "big"

# Optional endianess for the 2 bytes within a register
# Defaults to "big"
byte_endianess = "big"
},
# An float value created by reading an integer and applying an optional offset and scale
# This may span multiple registers
{
# Required type = "float"
type = "float"

# Required address of the lowest register
address = 0x52

# Required number of registers that should be joined to form the value
# A "float" value without the "integer_registers" settings is considered an IEEE 754 float, spanning 2 registers
integer_registers = 1

# Optional endianess for joining the 16-bit registers into a 32-bit value
# Defaults to "big"
word_endianess = "big"

# Optional endianess for the 2 bytes within a register
# Defaults to "big"
byte_endianess = "big"

# Optional scale that should be applied to the integer value
# Defaults to 1
scale = 10

# Optional offset that should be applied to the integer value after scaling
# Defaults to 0
offset = 2
}
)
}

out = {
signals = (
# All register mappings described for "in" except for "boolean" are supported in the "out" signals
{
type = "float"
address = 0x50

# Scale and offset a applied as attributes of the register that is written to
# This means the value written to "register" for a "signal" with "offset" and "scale" will be:
#
# register = (signal - offset) / scale
#
# It is fairly common to specify a scale and offset for modbus registers in a device manual
# You should be able to plug those values into this configuration without conversion
scale = 10
offset = 2
}
)
}
}
}